Specifications / Documents
- Dimensions: 1.75" (4.45cm) H x 19" (48.26cm) W x 12" (30.48cm) D
- Operating Temperature: 0° to 40° C
- Power Requirements: 100 to 240VAC, 47–63Hz, 1A; Power entry module with standard, grounded power cord supplied; 1A fuse protection
- Connectivity: Ethernet connection to ARC Plus; DB37 cables to IP-8 (not included)
- Channel Capacity: 8 metering, 8 status and 8 command channels per IP-8 (up to 2 IP-8s) Existing IP-8(s) required
- Metering Input Range: -4.5VDC to +4.5VDC
- Metering Input Accuracy: > 99.75% accuracy, full scale
- Status Input Range: > 0 to +28VDC or switch closure
- Output Types: 32 open collector outputs (16 raise, 16 lower); Maximum 250mA, 28V
Plus-X I/O Comparison Chart
| Plus-X IIU | Plus-X ICRU | Plus-X 300 | Plus-X 600 | Plus-X Dual IP-8 Adapter | |
| Number of metering inputs | 16 | 0 | up to 8** | 8 | 8 or 16*** |
| Number of status inputs | up to 32* | 0 | up to 8** | 16 | 8 or 16*** |
| Number of Form-C relays | 0 | 8 pairs | 8 | 6 pairs | 8 or 16 pairs*** |
* 16 dedicated status inputs, and 16 metering or status inputs
** 8 inputs, selectable as metering or status
*** The Plus-X Dual IP-8 Adapter uses the metering, status and relay channels from up to two existing ARC-16 IP-8s.