Overview
![]()
Tripp-Lite SU2200RTXLCD2U, SmartOnline 2000VA 1800W 120V Double-Conversion Sine Wave UPS, 2U Rack/Tower
2kVA 1.8kW 120V Battery Backup Protects Equipment against Damage, Downtime and Data Loss This on-line double-conversion UPS system maintains perfect output by converting AC input to DC, then reconverting UPS output to fully regulated sine wave AC. Constant on-line operation completely isolates sensitive equipment from every power problem on the AC line. The SmartOnline® SU2200RTXLCD2U provides the highest level of power protection and battery backup for education, healthcare, military, government and other mission-critical IT applications where space is limited, but premium power reliability is essential.
Features
- Offers network-grade protection against power failures and voltage fluctuations
- Zero transfer time between on-line and battery modes for uninterrupted operation
- Keeps equipment running during outages to allow time for file saves and safe shutdown
- Optional WEBCARDLXE network interface allows 24/7 remote access from anywhere
- 2-line front-panel LCD with 10 selectable screens reports detailed UPS and site power info
Specifications / Documents
- Input
- Input Phase: Single-Phase
- Rated input current (Maximum Load): 16A
- Nominal Input Voltage(s) Supported: 100V AC; 110V AC; 120V AC
- Nominal Input Voltage Description: 120V factory default
- UPS Input Connection Type: 5-20P
- UPS Input Cord Length (ft.): 8
- UPS Input Cord Length (m): 2.4
- Recommended Electrical Service: 120V
- Maximum Input Amps: 16
- Input Plug Type: NEMA 5-20P
- Input Current: 16A
- Power Factor (Input): 0.99
- Output
- Output Capacity: (VA) 2000
- Output Capacity: (kVA) 2
- Output Capacity: (Watts) 1800
- Output Capacity: (kW) 1.8
- Power Factor: 0.9
- Crest Factor: 3:1
- Nominal Voltage Details: 120V factory-default nominal voltage
- Frequency Compatibility: 50 / 60 Hz
- Load Management Receptacles: Two switchable two-outlet load banks
- Output AC Waveform (AC Mode): Pure Sine wave
- Output AC Waveform: (Battery Mode) Pure Sine wave
- Nominal Output Voltage(s) Supported
- 100V; 110V; 115V; 120V; 127V
- Output Receptacles: (6) 5-20R; (1) L5-20R
- Individually Controllable Load Banks: Yes
- Battery
- Battery Type: Valve Regulated Lead Acid (VRLA)
- Runtime Full Load: (min.) 7.7 min. (1800W)
- Runtime Half Load: (min.) 20.2 min. (900W)
- Expandable Runtime: Yes
- DC System Voltage (VDC): 72
- Battery Recharge Rate (Included Batteries): 3 hours recharge to 90%
- Battery Access: Battery access door
- Physical
- Primary Form: Factor Rackmount
- Rack Height: 2U
- Cooling Method: Fan
- Installation Form Factors Supported with Included Accessories: 4 post 19 inch rackmount
- Unit Dimensions (hwd / in.): 3.410 x 17.330 x 23.820
- Unit Weight (lbs.): 61.51
- Unit Weight (kg): 27.90